LOAD & RESISTANCE FACTOR DESIGN FOR BUILDING COLUMN
Plastic analysis of prismatic compression members in buildings is permitted if ( F y ) ½ (l/r) does not exceed 800 and F u £ 65 ksi (448 MPa). For axially loaded members with b/t £ l r , the maximum load P u , ksi (MPa= 6.894 X ksi), may be computed from
P u = 0.85A g F cr
WhereA g =gross cross-sectional area of the member
F cr =0.658 l F y for l £ 2.25
=0.877 F y / l for l > 2.25
l =(Kl / r) 2 (F y / 286,220)
The AISC specification for LRFD presents formulas for designing members with slender elements